Fire Resistance Cables

Fire Resistance Cables

A fire resistant cable is specially designed to transmit electrical energy in the extreme conditions that occur in a prolonged fire, guaranteeing the supply to emergency equipment such as signalling, smoke extractors, acoustic alarms, water pumps, etc.
Its use is recommended in emergency circuits in places of public concurrence such as: hospitals, airports, tunnels, subways, etc. as well as in offices, production plants, laboratories, etc.

A fire resistant cable ensures the integrity of essential services during a fire, complying with current regulations.

  • Emergency lighting.
  • Automatic door opening.
  • Video surveillance cameras.
  • Forced ventilation.
  • Inert network. Etc.

Conductor


Warning: Undefined variable $output in /home/almousacables/www/www/wp-content/themes/profiletree/functions.php on line 193

Conductor

Plain or tinned copper class 1 or class2 or class 5 stranded to IEC60228.

Insulation

GLASS MICA TAPE wrapped over the conductor and XLPE insulation type GP8 of BS 7655.1.3 or EI5 to BS EN 50363-5.

Color code

RED,YELLOW,BLUE , BLKACK or any other color upon request.

Assembly

Insulated cores assembled with suiatble fillers as required.

Inner sheath option

For armored cables a flame retardant low smoke halogen free sheath is extruded over the cable core under the armor.

Environmental protection

Lead sheath or a multilayer sheath AL/HDPE/PA in accordance with IEC 60502-1 and the provision of EN 50288-7 FOR MULTILAYER SHEATH.

Shielding

For VFD application or as required a shield of copper tape or a combination of copper tape and copper wires can be provided.

Armor

Galvanized steel wire or galvanised steel wire braid or galvanised steel tape armor option is available

Outer jacket

Flamner rertardant low smoke halogen free material type ST8 or LTS1 of BS 7655-6.1.

Print on the outer sheath (Example)

RSC POWER CABLE 4 X 50 MM2 0.6/1 KV IEC 60332-24 METER MARK OR

Standards

IEC 50502-1, IEC 60228, IEC 61034, IEC 60754- 1 & 2, IEC 60332-3-24 , IEC 60332-1-2, BS 7846, IEC 6-754-1&2, BS 8434-2, BS EN 50200

Technical Data


Warning: Undefined variable $output in /home/almousacables/www/www/wp-content/themes/profiletree/functions.php on line 222

Temperature range

70C, 90C, 105C

Voltage Grade

600/1000 VOLTS

Flame retardance /Fire resistance

IEC 60332-3-24, IEC 60332-1-2, IEC60332-3-24 , IEC 61034, IEC 60754-1& 2.BS 6387 cat C,W,Z, BS 5839, IEC 60331, BS 7846 F30, BS 7846 F60 , BS 7846 F120

Oil resistance

ICEA S-73-532

Sunlight resistance

UL 1581 SECTION 1200